Find out about our range of products:
Electrogear Products.
SEARCH

Schneider Contactor LC1D115** Coil 24VAC-415VAC) 3P(3 NO)115A. Price from:

LC1D115B7 24VAC

LC1D115F7 110VDC

LC1D115U7 240VAC

LC1D115N7 415VAC

SKU: SCH Categories: , ,
 

Schneider Electric LC1D TeSys D Contactors

TeSys D Contactors from Schneider Electric combine long mechanical and electrical life to offer a high reliable contactor. The range has been designed for integration in control systems and can be used to create motor starters for any type of application. The TeSys D contactors offer quick simple setup while maintaining compliance with international standards.

range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Motor control
Resistive load
utilisation category
AC-1
AC-4
AC-3
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit: <= 1000 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
115 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
motor power kW
30 kW at 220…230 V AC 50/60 Hz (AC-3)
55 kW at 380…400 V AC 50/60 Hz (AC-3)
59 kW at 415…440 V AC 50/60 Hz (AC-3)
75 kW at 500 V AC 50/60 Hz (AC-3)
80 kW at 660…690 V AC 50/60 Hz (AC-3)
65 kW at 1000 V AC 50/60 Hz (AC-3)
18.5 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
40 hp at 230/240 V AC 50/60 Hz for 3 phases motors
75 hp at 460/480 V AC 50/60 Hz for 3 phases motors
100 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
230 V AC 50/60 Hz
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
200 A (at 60 °C) for power circuit
Irms rated making capacity
1260 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 40 °C – 10 min for power circuit
550 A 40 °C – 1 min for power circuit
950 A 40 °C – 10 s for power circuit
1100 A 40 °C – 1 s for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
associated fuse rating
250 A gG at <= 690 V coordination type 1 for power circuit
200 A gG at <= 690 V coordination type 2 for power circuit
10 A gG for signalling circuit
average impedance
0.6 mOhm – Ith 200 A 50 Hz for power circuit
[Ui] rated insulation voltage
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability
0.8 Mcycles 200 A AC-1 at Ue <= 440 V
0.95 Mcycles 115 A AC-3 at Ue <= 440 V
power dissipation per pole
24 W AC-1
7.9 W AC-3
Front cover
With
mounting support
Rail
Plate
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
LROS (Lloyds register of shipping)
RINA
DNV
GOST
BV
GL
CCC
CSA
UL
UKCA
connections – terminals
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Power circuit: connector 1 cable(s) 10…120 mm²flexible without cable end
Power circuit: connector 2 cable(s) 10…50 mm²flexible without cable end
Power circuit: connector 1 cable(s) 10…120 mm²flexible with cable end
Power circuit: connector 2 cable(s) 10…50 mm²flexible with cable end
Power circuit: connector 1 cable(s) 10…120 mm²solid without cable end
Power circuit: connector 2 cable(s) 10…50 mm²solid without cable end
tightening torque
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 12 N.m – on connector hexagonal screw head 4 mm
operating time
6…20 ms opening
20…50 ms closing
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability
8 Mcycles
maximum operating rate
2400 cyc/h 60 °C
Complementary
coil technology
Built-in bidirectional peak limiting diode suppressor
control circuit voltage limits
0.3…0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8…1.15 Uc (-40…55 °C):operational AC 50/60 Hz
1…1.15 Uc (55…70 °C):operational AC 50/60 Hz
inrush power in VA
280…350 VA 60 Hz cos phi 0.8 (at 20 °C)
280…350 VA 50 Hz cos phi 0.8 (at 20 °C)
hold-in power consumption in VA
2…18 VA 60 Hz cos phi 0.3 (at 20 °C)
2…18 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation
3…8 W at 50/60 Hz
auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency
25…400 Hz
minimum switching current
5 mA for signalling circuit
minimum switching voltage
17 V for signalling circuit
non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm for signalling circuit
Environment
IP degree of protection
IP20 front face conforming to IEC 60529
protective treatment
TH conforming to IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-40…60 °C
60…70 °C with derating
ambient air temperature for storage
-60…80 °C
operating altitude
0…3000 m
fire resistance
850 °C conforming to IEC 60695-2-1
flame retardance
V1 conforming to UL 94
mechanical robustness
Vibrations contactor open: 2 Gn, 5…300 Hz
Vibrations contactor closed: 4 Gn, 5…300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 6 Gn for 11 ms
height
158 mm
width
120 mm
depth
136 mm
net weight
2.5 kg
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
2.482 kg
Package 1 Height
17 cm
Package 1 width
18.5 cm
Package 1 Length
20.5 cm
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
EU RoHS Directive
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
Circularity Profile
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free
Yes
Contractual warranty
Warranty
18 months