Find out about our range of products:
Electrogear Products.
SEARCH

Schneider Contactor LC1D150** Coil 24VAC-415VAC) 3P(3 NO)150A. Price From:

LC1D150B7 24VAC

LC1D150F7 110VAC

LC1D150U7 240VAC

LC1D150N7 415VAC

 

 

Categories: , ,
 

Schneider Electric LC1D TeSys D Contactors

TeSys D Contactors from Schneider Electric combine long mechanical and electrical life to offer a high reliable contactor. The range has been designed for integration in control systems and can be used to create motor starters for any type of application. The TeSys D contactors offer quick simple setup while maintaining compliance with international standards.

range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Motor control
Resistive load
utilisation category
AC-3
AC-4
AC-1
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit: <= 1000 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
150 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
motor power kW
40 kW at 220…230 V AC 50/60 Hz (AC-3)
75 kW at 380…400 V AC 50/60 Hz (AC-3)
80 kW at 415…440 V AC 50/60 Hz (AC-3)
90 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 660…690 V AC 50/60 Hz (AC-3)
75 kW at 1000 V AC 50/60 Hz (AC-3)
22 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
40 hp at 200/208 V AC 50/60 Hz for 3 phases motors
50 hp at 230/240 V AC 50/60 Hz for 3 phases motors
100 hp at 460/480 V AC 50/60 Hz for 3 phases motors
125 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
230 V AC 50/60 Hz
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
200 A (at 60 °C) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1660 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity
1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 40 °C – 10 min for power circuit
580 A 40 °C – 1 min for power circuit
1200 A 40 °C – 10 s for power circuit
1400 A 40 °C – 1 s for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1
315 A gG at <= 690 V coordination type 1 for power circuit
250 A gG at <= 690 V coordination type 2 for power circuit
average impedance
0.6 mOhm – Ith 200 A 50 Hz for power circuit
[Ui] rated insulation voltage
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability
0.85 Mcycles 150 A AC-3 at Ue <= 440 V
1 Mcycles 200 A AC-1 at Ue <= 440 V
power dissipation per pole
24 W AC-1
13.5 W AC-3
Front cover
With
mounting support
Plate
Rail
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
DNV
GOST
RINA
UL
CSA
LROS (Lloyds register of shipping)
GL
CCC
BV
UKCA
connections – terminals
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Power circuit: connector 1 cable(s) 10…120 mm²flexible without cable end
Power circuit: connector 2 cable(s) 10…50 mm²flexible without cable end
Power circuit: connector 1 cable(s) 10…120 mm²flexible with cable end
Power circuit: connector 2 cable(s) 10…50 mm²flexible with cable end
Power circuit: connector 1 cable(s) 10…120 mm²solid without cable end
Power circuit: connector 2 cable(s) 10…50 mm²solid without cable end
tightening torque
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 12 N.m – on connector hexagonal screw head 4 mm
operating time
20…35 ms closing
40…75 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability
8 Mcycles
maximum operating rate
1200 cyc/h 60 °C
Complementary
coil technology
Built-in bidirectional peak limiting diode suppressor
control circuit voltage limits
0.3…0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8…1.15 Uc (-40…55 °C):operational AC 50/60 Hz
1…1.15 Uc (55…70 °C):operational AC 50/60 Hz
inrush power in VA
280…350 VA 60 Hz cos phi 0.9 (at 20 °C)
280…350 VA 50 Hz cos phi 0.9 (at 20 °C)
hold-in power consumption in VA
2…18 VA 60 Hz cos phi 0.9 (at 20 °C)
2…18 VA 50 Hz cos phi 0.9 (at 20 °C)
heat dissipation
3…4.5 W at 50/60 Hz
auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency
25…400 Hz
minimum switching current
5 mA for signalling circuit
minimum switching voltage
17 V for signalling circuit
non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm for signalling circuit
Environment
IP degree of protection
IP20 front face conforming to IEC 60529
protective treatment
TH conforming to IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-40…60 °C
60…70 °C with derating
ambient air temperature for storage
-60…80 °C
operating altitude
0…3000 m
fire resistance
850 °C conforming to IEC 60695-2-1
flame retardance
V1 conforming to UL 94
mechanical robustness
Vibrations contactor open: 2 Gn, 5…300 Hz
Vibrations contactor closed: 4 Gn, 5…300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 6 Gn for 11 ms
height
158 mm
width
120 mm
depth
136 mm
net weight
2.5 kg
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
2.491 kg
Package 1 Height
17 cm
Package 1 width
18.5 cm
Package 1 Length
20.5 cm
Unit Type of Package 2
P06
Number of Units in Package 2
27
Package 2 Weight
79.96 kg
Package 2 Height
80 cm
Package 2 width
80 cm
Package 2 Length
60 cm
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
EU RoHS Directive
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
Circularity Profile
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free
Yes
Contractual warranty
Warranty
18 months