Schneider Electric LC1D TeSys D Contactors

TeSys D Contactors from Schneider Electric combine long mechanical and electrical life to offer a high reliable contactor. The range has been designed for integration in control systems and can be used to create motor starters for any type of application. The TeSys D contactors offer quick simple setup while maintaining compliance with international standards.

range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Resistive load
Motor control
utilisation category
AC-3
AC-1
AC-4
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current
25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
motor power kW
3 kW at 220…230 V AC 50/60 Hz (AC-3)
5.5 kW at 380…400 V AC 50/60 Hz (AC-3)
5.5 kW at 415…440 V AC 50/60 Hz (AC-3)
7.5 kW at 500 V AC 50/60 Hz (AC-3)
7.5 kW at 660…690 V AC 50/60 Hz (AC-3)
3.7 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
24 V AC 50/60 Hz
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
25 A (at 60 °C) for power circuit
10 A (at 60 °C) for signalling circuit
Irms rated making capacity
250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
105 A 40 °C – 10 s for power circuit
210 A 40 °C – 1 s for power circuit
30 A 40 °C – 10 min for power circuit
61 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1
40 A gG at <= 690 V coordination type 1 for power circuit
25 A gG at <= 690 V coordination type 2 for power circuit
average impedance
2.5 mOhm – Ith 25 A 50 Hz for power circuit
[Ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability
2 Mcycles 12 A AC-3 at Ue <= 440 V
0.8 Mcycles 25 A AC-1 at Ue <= 440 V
power dissipation per pole
0.36 W AC-3
1.56 W AC-1
Front cover
With
mounting support
Rail
Plate
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
CCC
CSA
GL
GOST
BV
DNV
RINA
LROS (Lloyds register of shipping)
UL
connections – terminals
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
tightening torque
Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
operating time
12…22 ms closing
4…19 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability
15 Mcycles
maximum operating rate
3600 cyc/h 60 °C
Complementary
coil technology
Without built-in suppressor module
control circuit voltage limits
0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8…1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85…1.1 Uc (-40…60 °C):operational AC 60 Hz
1…1.1 Uc (60…70 °C):operational AC 50/60 Hz
inrush power in VA
70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA
7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation
2…3 W at 50/60 Hz
auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency
25…400 Hz
minimum switching current
5 mA for signalling circuit
minimum switching voltage
17 V for signalling circuit
non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm for signalling circuit
Environment
IP degree of protection
IP20 front face conforming to IEC 60529
protective treatment
TH conforming to IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-40…60 °C
60…70 °C with derating
ambient air temperature for storage
-60…80 °C
operating altitude
0…3000 m
fire resistance
850 °C conforming to IEC 60695-2-1
flame retardance
V1 conforming to UL 94
mechanical robustness
Vibrations contactor open: 2 Gn, 5…300 Hz
Vibrations contactor closed: 4 Gn, 5…300 Hz
Shocks contactor open: 10 Gn for 11 ms
Shocks contactor closed: 15 Gn for 11 ms
height
77 mm
width
45 mm
depth
86 mm
net weight
0.325 kg
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
359 g
Package 1 Height
5 cm
Package 1 width
9 cm
Package 1 Length
11 cm
Unit Type of Package 2
S02
Number of Units in Package 2
20
Package 2 Weight
7.655 kg
Package 2 Height
15 cm
Package 2 width
30 cm
Package 2 Length
40 cm
Unit Type of Package 3
P06
Number of Units in Package 3
320
Package 3 Weight
130.66 kg
Package 3 Height
80 cm
Package 3 width
80 cm
Package 3 Length
60 cm
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
REACh free of SVHC
Yes
EU RoHS Directive
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure
Circularity Profile
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free
Yes
Contractual warranty
Warranty
18 months